Product function
*Split core type structure, which can be installed without changing cables
*High-quality epoxy resin vacuum casting, excellent mechanical and environmental *resistance
*High-quality stainless steel clamp hoop fastening structure, easy and reliable installation
*Output terminal type, more concise wiring
*Single winding protection current transformer
TECHNICAL PARAMETERS
Dimensions (D×d×H) |
153mm×105mm×83mm |
|
Rated frequency |
50Hz |
|
Rated secondary current |
5A |
|
Rated burden |
≤2.5VA |
|
Applicable cable outer diameter |
≤φ94mm |
|
Rated primary current range |
100A |
|
Dielectric strength |
AC3000V,1min |
|
Rated continuous overcurrent |
120% of rated current |
|
Polarity and homonym |
P2 represents the primary polarity terminal, S1, S2 represent the secondary polarity end, P2 and S2 have the same polarity (-polarity) at the same instant |
|
Working environment |
Temperature |
-25℃~40℃ |
Humidity |
≤90% |
|
Altitude |
≤1000m |
TECHNICAL DATA
Model |
LXZK1 |
||||
Accuracy class & Rated burden(VA) |
Accuracy class & Rated burden(VA) |
||||
Type |
Current transformer for protection |
Current transformer for measurement |
|||
Current rating |
5P10 |
10P10 |
0.5 |
1.0 |
3 |
20/1 |
|
1 |
|
|
√ |
50/1 |
1 |
1.5 |
|
√ |
√ |
75/1 |
1.5 |
2.5 |
|
√ |
√ |
100/1 |
2.5 |
3.75 |
|
√ |
√ |
150/1 |
2.5 |
5 |
√ |
√ |
√ |
50/5 |
|
1 |
|
|
√ |
75/5 |
1 |
1.5 |
|
√ |
√ |
100/5 |
1.5 |
2.5 |
|
√ |
√ |
150/5 |
2.5 |
3.75 |
|
√ |
√ |
ORDERING INFORMATION